In brief
OT security protects controllers, operator panels, SCADA and the production network, where process continuity and human safety matter most, not data confidentiality. The foundation is segmentation: splitting the plant into zones connected by controlled conduits, with a target security level for each zone, as described in IEC 62443-3-2. The first steps are an asset inventory, separating OT from IT with an intermediate zone, one logged remote access channel for vendors and backups of controller configurations.
How OT differs from IT
OT (operational technology) covers systems that monitor and control physical processes: PLCs, drives, robots, HMI panels, SCADA and building automation. NIST SP 800-82 Rev. 3 describes how to secure such systems while respecting their performance, reliability and safety requirements. The differences from IT are practical:
| Feature | Office IT | OT in the plant |
|---|---|---|
| What matters most | data confidentiality and integrity | process availability and human safety |
| Updates | monthly, automatic | in maintenance windows, after the machine vendor approves |
| Hardware lifetime | a few years | often fifteen years or more |
| Active scanning | routine | can freeze an older controller |
| Protocols | encrypted, with authentication | many older ones without authentication |
| Recovery after an incident | restore from backup | restore, plus line restart and quality checks |
That is why office methods do not carry over to the shop floor one to one. A vulnerability scanner run on the controller network in the middle of a shift can stop a line more effectively than an attacker.
The ISA/IEC 62443 series: who reads which part
ISA/IEC 62443 is a series of standards on the security of industrial automation and control systems (IACS). It splits responsibilities between the asset owner, service providers and product suppliers:
| Part | What it covers | For whom |
|---|---|---|
| 62443-2-1 | security program | asset owner |
| 62443-2-4 | requirements for service providers | integrators, service |
| 62443-3-2 | risk assessment, zones and conduits | asset owner with the integrator |
| 62443-3-3 | system requirements and security levels | integrator, system designer |
| 62443-4-1 | secure product development lifecycle | device and software manufacturers |
| 62443-4-2 | technical requirements for components | manufacturers of controllers, panels, gateways |
A mid-sized plant starts with parts 3-2 and 2-1, and can require machine vendors and integrators to comply with 2-4 and 4-2. It is a useful language for contract clauses and requests for proposal.
Zones and conduits in practice
IEC 62443-3-2 describes the process: define the system under consideration, partition it into zones and conduits, assess the risk of each zone and conduit, set a target security level for each and document the requirements. A zone is a group of assets with similar security requirements, a conduit is a controlled communication path between zones.
An example split for a mid-sized plant:
- line 1 zone and line 2 zone: the controllers, drives and panels of one line, with no communication between lines;
- supervision zone: SCADA, the MES server, the historian, the MQTT broker;
- industrial demilitarized zone (DMZ): a relay server for data going to ERP, a jump server for remote access, an update repository;
- office zone: ERP, email, staff computers.
The conduit rule: nothing connects directly from the office to a controller. ERP talks to MES through the DMZ, the vendor's service engineer comes in through a jump server with session recording, and every flow between zones is on an allowlist with a justification. The logic is similar to zero trust architecture, only with more weight on availability.
Security levels SL 1–4
IEC 62443-3-3 maps technical requirements to seven foundational requirements: identification and authentication control, use control, system integrity, data confidentiality, restricted data flow, timely response to events and resource availability. Each requirement has variants for four security levels:
| Level | What it protects against |
|---|---|
| SL 1 | casual or coincidental violation |
| SL 2 | intentional attack with simple means, generic skills and low resources |
| SL 3 | intentional attack with sophisticated means and knowledge of industrial systems |
| SL 4 | intentional attack with sophisticated means, extended resources and high motivation |
The standard distinguishes the target level of a zone (SL-T), the level a given system is capable of (SL-C) and the level actually achieved. The gap between target and achieved is your work list. A zone with welding robots does not need the same level as a zone with a chemical installation.
Where to start in a mid-sized plant
- Inventory. List devices, firmware and connections. Passive traffic monitoring is safer than active scanning.
- An intermediate zone between OT and IT. The first firewall and the first allowlist of flows.
- Remote access. One channel for all machine vendors, with multi-factor authentication, session approval by the plant and recording.
- Backup and recovery. Backups of controller programs and panel configurations, stored outside the OT network, with a test restore.
- Monitoring. Passive analysis of industrial traffic that alerts on a new device or a write to a controller outside a maintenance window.
- Vulnerabilities. Updates in maintenance windows, and where that is impossible, compensating controls: restricting traffic, disabling unused services. The process is covered in more depth in the article on vulnerability management.
That is what the NIS2 and OT network segmentation program at a chemical plant looked like.
The NIS2 Directive covers, among others, selected manufacturing sectors and the chemical and food industries, including medium-sized companies. The obligations are described in the article NIS2: obligations for IT. Manufacturers of devices with software are also affected by the Cyber Resilience Act.
Questions and answers
Is IEC 62443 mandatory?
The standard itself is not law. It becomes a requirement when a customer, an insurer or a machine vendor contract writes it in. It is also a convenient way to show that a plant covered by NIS2 applies appropriate risk management measures on its production network. That is why many plants follow its structure without formal certification.
Can you scan an OT network with a vulnerability scanner?
Carefully. Active scanning can freeze older controllers and panels, so on a production network you start with passive traffic analysis and an inventory built from documentation. Active tests are done in a maintenance window, on selected devices, with production's agreement, and ideally first on a spare device or in a lab.
How do you secure remote access for a machine vendor's service team?
With one channel for all vendors, through a jump server in the intermediate zone. Each service engineer has a personal account with multi-factor authentication, a plant employee enables the session for a set time and the session is recorded. Vendor modems and routers connected directly to machines need to be listed and either disconnected or moved into that channel.
How does the Purdue model differ from zones and conduits?
The Purdue model, on which ISA-95 is based, splits a plant into functional levels from the physical process up to ERP. Zones and conduits from IEC 62443 split it by security requirements and risk. Purdue levels are a good starting point for drawing zones, but one zone can span several levels and one level can be divided into many zones.